ANALYSIS OF GAS CONTENT DYNAMICS IN POWER TRANSFORMERS DURING DEVELOPMENT OF SPARK DISCHARGE

Abstract

The results of analysis of the dynamics of change in the values of diagnostic criteria used to recognise the type of defect based on the dissolved gas analysis results for five high-voltage transformers during the development of spark discharges are presented. In the course of the analysis the dynamics of changes in gas concentrations and defect nomograms were considered. There was also analysed the change of the defect type during the spark discharges development by means of diagnostic space determined by gas ratios values according to IEC 60599 and ETRA square, and by means of diagnostic space determined by gas percentage content according to Duval's triangle. According to the results of the analysis it was found that during the development of spark discharges in different transformers the values of diagnostic criteria correspond to the defects of different types, which makes it practically impossible to predict this defect based on the results of previous tests. At the same time the values of both gas ratios and gas percentage as well as defect nomograms obtained by dissolved gas analysis before the moment when gas concentrations exceeded their limit values correspond to the defects of different types, which enables to recognise spark discharges at an early stage. Analysis of correlation relations between values of concentrations and percentages of gases and the operation time as well as between the values of concentrations and percentages of individual gases shows that the development of spark discharges is accompanied not only by the growth of gas concentrations, which is known and widely used, but there is also a significant positive correlation between the values of concentrations of dissolved gases in oil and the operation time as well as between concentrations of individual gases. At the same time, the gases between which a significant correlation has been detected during the development of spark discharges in different transformers differ significantly. The analysis showed that the standards and criteria of IEC 60599, the ETRA square and the Duval triangle do not allow any spark discharges to be detected. The maximum recognition reliability was obtained using the nomogram method. The results show that an early detection of spark discharges is possible, which increases the reliability of nondestructive diagnostics and prolongs the service life of transformers.

Authors and Affiliations

Oleg Volodymyrovych Shutenko, Igor Volodymyrovych Barbashov, Halyna Viktorivna Omelianenko

Keywords

Related Articles

ANALYSIS OF THE DIAGNOSTIC CRITERIA USED TO DEFECT TYPE RECOGNITION BASED ON THE RESULTS OF ANALYSIS OF GASES DISSOLVED IN OIL

Dissolved gas analysis is one of the most used and common diagnostic methods for high voltage oil-filled equipment. According to existing methods for interpreting the results of dissolved oil gas analysis, defect types a...

ЕКСПЕРИМЕНТАЛЬНІ ДОСЛІДЖЕННЯ ФАКТОРІВ ВПЛИВУ НА ГЕНЕРАЦІЮ СОНЯЧНОЇ ЕЛЕКТРОСТАНЦІЇ

Інтенсивний розвиток мережевих сонячних електростанцій призводить до значних проблем управління та надійності роботи електричних систем країни, внаслідок стохастичного характеру погодних явищ, таких як хмарність, інтенси...

МАТЕМАТИЧНІ МОДЕЛІ ДІАГНОСТИКИ БОЛТОВОГО СТРУМОПРОВІДНОГО З’ЄДНАННЯ В УМОВАХ РЕЖИМНИХ ПАРАМЕТРІВ, ЩО ЗМІНЮЮТЬСЯ

Надійність передачі і розподілу електроенергії в портах, на суднах та енергетичних підприємствах залежить від стану болтових струмопровідних з’єднань. Практика експлуатації показує, що 2 % випадків аварійних зупинок техн...

ВИЗНАЧЕННЯ ГРАНИЧНОГО ЗНАЧЕННЯ НАПРУГИ В ТОЧЦІ ПРИЄДНАННЯ СОНЯЧНОЇ ЕЛЕКТРОСТАНЦІЇ

Для побутових сонячних електростанцій не розраховують режими електричної мережі. Відомо, що напруга в точці встановлення сонячної електростанції може перевищувати допустиму. Таке підвищення напруги спричиняє вихід електр...

Аналіз основних підходів, методів вибору і обґрунтування параметрів та режимів вітроенергетичних установок для інтеграції в роботу електроенергетичної системи

Одним з пріоритетних напрямків розвитку електроенергетики для України є освоєння та використання альтернативних і відновлюваних джерел енергії, що веде до зменшення залежності від імпорту електричної енергії. Велика част...

Download PDF file
  • EP ID EP704053
  • DOI https://doi.org/10.20998/2224-0349.2021.02.07
  • Views 106
  • Downloads 0

How To Cite

Oleg Volodymyrovych Shutenko, Igor Volodymyrovych Barbashov, Halyna Viktorivna Omelianenko (2021). ANALYSIS OF GAS CONTENT DYNAMICS IN POWER TRANSFORMERS DURING DEVELOPMENT OF SPARK DISCHARGE. Вісник Національного технічного університету «ХПІ». Серія: Енергетика: надійність та енергоефективність, 3(2), -. https://europub.co.uk./articles/-A-704053