Analysis of the influence of drydock main pumps drive on electric network
Journal Title: Восточно-Европейский журнал передовых технологий - Year 2019, Vol 5, Issue 8
Abstract
<p>The influence of unadjustable-speed AC drive and adjustable-speed DC drive of the drydock main pumps on the network of the Okean shipyard (Ukraine) is investigated in MatLab SimPowerSystems.</p><p>To accurately simulate deep-bar induction motors, the own method of determining the parameters of the T-shaped equivalent circuit and viscous friction coefficient of a virtual motor according to catalog data is used. This method is based on formulas that correspond to the T-shaped and refined L-shaped equivalent circuit. It is proposed to introduce the corrected values of the initial starting and critical torque ratio into the calculation. The rated power factor is determined indirectly and compared with the catalog value. The dependences of rotor resistance are approximated by elementary functions, which provide almost constant values of these parameters at subcritical slip values.</p><p>As a result of the simulation, it became clear that even with the alternate starting of unregulated electric pump units, there is a significant voltage drop in the network.</p><p>The mathematical model of DC drives was built with a common dual-circuit automatic speed control system. A resonance filter is included at the input of each synchronized 6-pulse generator, thereby eliminating possible errors in operation.</p><p>The simulation results prove that during the operation of DC drives, there are switching voltage variations in the network, substantially non-sinusoidal current consumption and reactive power consumption. Given the stray capacitance of the cable line, high-frequency voltage fluctuations occur, which are dangerous for electric equipment.</p>Through the use of the harmonic filtering and reactive power control device, these negative phenomena can be eliminated, thus, the DC drive will surpass unadjustable-speed induction motor drive in many respects. To minimize reactive power consumption, an automatic control system with an integrated variable gain reactor power controller can be used
Authors and Affiliations
Pavel Khristo
Research into the recovery of exhaust gases from ice using an expansion machine and fuel conversion
<p>We have devised a scheme for the energy-generating unit based on the internal combustion engine 1Ch 6.8/5.4 with a spark ignition and a two-stage system for the recovery of heat from the exhaust gases. The basic eleme...
Substantiation of the development of formulations for organic cupcakes with an elevated protein content
<p class="a">In order to develop the formulations for organic cupcakes with an elevated protein content, we examined and analyzed the amino acid composition of four samples of flour: wheat flour, organic wheat flour, org...
Development of a spatialdynamical model of the structure of clumps of toxic cyanobacteria for biosafty purposes
<p class="a">We have devised a spatialdynamic model that describes the structure of clusters of toxic cyanobacteria over large water areas. The application of the constructed model has been demonstrated in order to iden...
Development of the interacting agents behavior scenario in the cyber security system
The results of modeling and analysis of scenarios of the behavior of interacting agents in conditions of cyber conflict are presented. General approaches to the development of a scenario of the behavior of antagonistic a...
Devising methodological provisions for the comparative evaluation of variants for an armament sample in terms of military-technical level
<p>When setting a tactical-technical task on constructing a sample of armament, not only its characteristics related to purpose are considered, but its operational and technical, technological, economic, and other charac...