ESTIMATING PERFORMANCE OF AIR - COOLED SCREW CHILLER BY LOWERING CONDENSOR TEMPERATURE

Abstract

This paper presents performance enhancement of air - cooled screw chiller by using cooling tower exhaust air. The chiller was tripping in peak summer on high discharge pressure. After finding out the reason a additional ducting arrangement was provided from cooling tower exhaust to air - cooled screw chiller condenser. This ducting arrangement can discharge exhaust air from cooling tower to air cooled screw chiller conden ser. Study was carried out in various seasons like peak summer, winter, monsoon, and to find the enhancement of Coefficient of Performance (COP) for screw chiller. After providing ducting arrangement the tripping of air cooled screw chiller stopped, also C OP improved. The COP can be improved approx. 16 % in peak summer by using this duct arrangement system

Authors and Affiliations

Sharad Chaudhary*

Keywords

Related Articles

A REVIEW OF LITERATURE ON THERMAL DESIGN OF FORCED DRAFT COUNTER TO CROSS FLOW AIR COOLED HEAT EXCHANGER

Heat exchangers are equipment that transfers heat from one medium to another. An air cooled heat exchanger, or ACHE, is simply a pressure vessel which cools a circulating fluid within finned tubes by forcing ambient air...

 A REVIEW OF GENETIC ALGORITHMS AND ITS APPLICATIONS IN CHEMICAL ENGINEERING RESEARCH

 This paper presents a review of Genetic Algorithms (GAs) and its applications within the field of Chemical Engineering. The primary applications of GAs in Chemical Engineering date back to the 1970s, and within th...

VIOLA JONES AND SIFT FRAMEWORK FOR FACE RECOGNITION

Faces are highly deformable objects which can easily change their appearance over time. All face areas are not subjected to the same variability. Hence decoupling the information from independent areas of the face is of...

 DEVELOPMENT OF A SUSTAINABLE CONCRETE WASTE RECYCLING SYSTEM

 Construction solid waste has caused serious environmental problems. Reuse, recycling and reduction of construction materials have been advocated for many years, and various methods have been investigated. There ma...

Download PDF file
  • EP ID EP163784
  • DOI -
  • Views 97
  • Downloads 0

How To Cite

Sharad Chaudhary* (0). ESTIMATING PERFORMANCE OF AIR - COOLED SCREW CHILLER BY LOWERING CONDENSOR TEMPERATURE. International Journal of Engineering Sciences & Research Technology, 4(8), 636-643. https://europub.co.uk./articles/-A-163784