ESTIMATING PERFORMANCE OF AIR - COOLED SCREW CHILLER BY LOWERING CONDENSOR TEMPERATURE

Abstract

This paper presents performance enhancement of air - cooled screw chiller by using cooling tower exhaust air. The chiller was tripping in peak summer on high discharge pressure. After finding out the reason a additional ducting arrangement was provided from cooling tower exhaust to air - cooled screw chiller condenser. This ducting arrangement can discharge exhaust air from cooling tower to air cooled screw chiller conden ser. Study was carried out in various seasons like peak summer, winter, monsoon, and to find the enhancement of Coefficient of Performance (COP) for screw chiller. After providing ducting arrangement the tripping of air cooled screw chiller stopped, also C OP improved. The COP can be improved approx. 16 % in peak summer by using this duct arrangement system

Authors and Affiliations

Sharad Chaudhary*

Keywords

Related Articles

[i][/i] NON-LINEAR PUSHOVER ANALYSIS OF RCC BUILDING WITH BASE ISOLATION SYSTEM

 Buildings are designed as per the code regulations meeting all specific requirements of code and assuming a linear elastic behaviour for the structural members. Moreover, it is also necessary to know the behav...

A Cascaded Quasi Z-Source Scheme Step up DC-DC Converter Using ANN Based Control

Modern renewable generation systems need smart and integrated power converters ensure for high efficiency of power conversion .This project intends to the Artificial Neural Network (ANN) based control step up DC-DC con...

 GRAPHICAL IMAGE AS AUTHENTICATION APPROACH IN CLOUD COMPUTING

 Graphical password is easy to remember as compared to alphanumerical password. Users tend to pick passwords that can be easily guessed. In case, if user choose hard then it is difficult to remember. Graphical pass...

 Social Network Analysis in Information Retrieval System

 A social network is a social structure made up of a set of actors (such as individuals or organizations) and the dyadic ties between these actors. The social network perspective provides a clear way of analyzing t...

PERFORMANCE ANALYSIS OF INTEGRATED PACKED BED SOLAR FLAT PLATE COLLECTOR

The main objective of this paper is to study the performance of a solar flat plate collector - packed bed system by using various secondary working fluids such as water, air. In the pr...

Download PDF file
  • EP ID EP163784
  • DOI -
  • Views 109
  • Downloads 0

How To Cite

Sharad Chaudhary* (0). ESTIMATING PERFORMANCE OF AIR - COOLED SCREW CHILLER BY LOWERING CONDENSOR TEMPERATURE. International Journal of Engineering Sciences & Research Technology, 4(8), 636-643. https://europub.co.uk./articles/-A-163784