TEMPERATURE DEPENDENCE OF THE DIELECTRIC LOSS FACTOR OF OIL-IMPREGNATED CONDENSER INSULATION FOR THE DIAGNOSIS OF HIGH-VOLTAGE APPARATUS IN THE ONLINE MODE
Journal Title: Електромеханічні і енергозберігаючі системи - Year 2017, Vol 4, Issue 40
Abstract
Purpose. To assess the possibility of using of temperature dependences of the basic diagnostic parameters of main insulation of apparatus with condenser oil impregnated paper insulation during estimation of their technical state, to develop a mathematical model for online monitoring systems under the operating voltage. Methodology. We have applied the experimental observations with subsequent statistical processing of data, approximation of temperature dependences, and also calculation of correlation relationships. Experimental observations carried out by the method of online monitoring under the operating voltage ("online") of a group of 17 oil-filled 330 kV bushings, the observation period from 12 to 20 months, the insulation temperature range –20 ... +33 °С. Results. The research made it possible to develop an improved mathematical model for evaluating the technical state of apparatus with condenser oil impregnated paper insulation, first of all bushings and instrument current transformers, which makes it possible to more accurately detect defects in the insulation of apparatuses. Originality. The improved model was developed for calculating the temperature coefficient for insulation with a low moisture content (0.5 %) of solid insulation in the operating temperature range, which was not taken into account in previous researchers. The research justify the futility of temperature reduction of the value of the insulation power loss factor, since the function of the temperature dependence for apparatus with hidden defects can differ significantly from the formula used for such a reduction, and for zero defects, the value given to 20°C will practically not be different from the one obtained at operating temperature. Therefore, we recommended that to refrain from temperature reduction of the insulation power loss factor. Practical value. This model is used in microprocessor-based automated monitoring systems to increase the probability of detecting defects in the main insulation of high voltage apparatus with OIP insulation.
Authors and Affiliations
Оleksandr Sakhno, Lydmila Skrupskaya
THE RESEARCH ON FREQUENCY-CONTROLLED ELECTRIC DRIVE OPERATION MODES UNDER FAULT-TOLERANT CONTROL
Purpose. In the paper the results of research on developed systems for fault-tolerant vector control, which ensure operability of frequency-controlled electric drive with presence of damages in power circuit of induction...
ACCURACY ESTIMATION OF THE EQUIVALENT CIRCUIT PARAMETERS IDENTIFICATION OF SQUIRREL CAGE INDUCTION MOTOR
Purpose. To estimate the accuracy of T-shaped equivalent circuit parameters estimation of the squirrel cage induction motor taking into account errors in the initial experimental data. This will allow formulating the con...
DEVELOPMENT TRENDS AND IMPROVEMENT WAYS OF A WIND TURBINE SIMULATION SYSTEMS
Purpose. To systematize the approaches to synthesis of wind turbine simulators and to develop the recommendations for the improvement of these systems. Methodology. Based on a comprehensive literature review, the general...
PECULIARITIES OF THE CREATING OF ELECTROMAGNETIC VIBRATION DRIVE SYSTEMS MATHEMATICAL MODELS
Relevance of the work. Electromagnetic vibrating drive systems are used on vibrating conveyors, feeders and other vibro-technological devices that require automatic regulation of vibration parameters during operation. Th...
FEATURES OF THE NUMERICAL SOLUTION OF DIFFERENTIAL EQUATIONS OF THE MODEL ELECTROMECHANICAL SYSTEMS IN SOFTWARE ENVIRONMENT MATLAB
Purpose. The scientific work is devoted to the research of electromechanical systems by means of their modeling using the software environment Matlab. Originality. The features of obtaining a numerical solution in the so...